Sign In | Join Free | My hardware-wholesale.com
China Wenzhou New Blue Sky Electrical Co.,Ltd logo
Wenzhou New Blue Sky Electrical Co.,Ltd
Wenzhou New Blue Sky Electrical Co.,Ltd Focusing on Circuit Breaker manufacturing High quality materials, professional production
Active Member

7 Years

Home > RCBO Breaker >

NBSM7-45L C16 Residual Current Circuit Device , Residual Current Switch MEM RCBO

Wenzhou New Blue Sky Electrical Co.,Ltd
Contact Now

NBSM7-45L C16 Residual Current Circuit Device , Residual Current Switch MEM RCBO

  • 1
  • 2

Brand Name : NBSe/OEM

Model Number : NBSM7-45L

Certification : CE

Place of Origin : CHINA

Shell Material : PA66

Rated Voltage : 240V

Rated Current : 6,10,16,20,25,32A

Protection : MCB+RCD

Frequency : 50/60Hz

Standard : EN60947-2

Mounting : Plug-in type

Triping : Electronic type

Product name : RCBO,Electrical RCCB/RCD/ELCB

Material : Copper,High Standard Plastic Sliver Copper,T2 Red Copper / Silvering

Application : household,Terminal distribution,Electrical Power,widely,Electricity Distribution Room

Tripping curve : C,B,D curve

Residual current : 10mA,30mA,

Contact Now

NBSe NBSM7-45L C16 Residual Current Circuit Breaker with Overload Protection,MEM RCBO

1. General description

This unit combines the overcurrent protection of the "MEMGUARD"mcb with an electronic r.c.d capable of high sensitivity operation with special fail-safe features.The unit is ready for installation in"MEMGUARD"SPN type A or type B boards operating on single phase 240V system. The unit provides single-phase protection against overload ,short circuit and earth leakage currents.

2. OVERCURRENT PROTECTION

Overcurrent protection to circuit conductors is provided by thermal and magnetic tripping elements is the line side ,equivalent to the "MEMGUARD"mcb and is available in both M3 & M6 versions.Operating characteristice on overcurrent (the time/current curves)are as for the "MEMGUARD"standard m.c.b..This section of the unit complies with the requirements of BSEN60947-2 for miniature circuit breakers,Short circuit requirements comply with BS4293.

3. EARTH FAULT PROTECTION

The r.c.d elment of the device provides core-balance detecton of the difference between line and neutral currents and amplificaton to provide high sensitivity.

4. OPERATION OF THE TEST BUTTON

This check is made aftor installation with all shields and covers in place ,and requires the MCB/RCD and the main supply switched on Pressing hte button marked "T" on the MCB/RCD applies a simulated earth-fault to the MCB/RCD whichshould trip instantly.
This should be checkde frequently, at least quarterly. If the MCB/RCD fails to trip seek expert advice.


NOTE:
Operation of the test device checks only the correct functoninge of the MCB/RCD at a higher currect than the rated tripping level.This test does not check the integrity of the earthinge system

NBSM7-45L C16 Residual Current Circuit Device , Residual Current Switch MEM RCBO


5. INSTALLATION

1). Fit MCB/RCD unit as required into "MEMGUARD"consumer/distribution board.
2). The BLACK flying neutral supply lead must be connected to the Neutral supply terminal block.
3). The LOAD connections are made to the outgoing terminals of the unit marked 'L"LOAD and "load.
NOTE:The neutr al supply terminal block.
4). High voltage insulation testers must not be used with the unit in circuit.to carry out hv tests disconnect load side cables from MCB/RCD unit and test circuit as normal.

NBSM7-45L C16 Residual Current Circuit Device , Residual Current Switch MEM RCBO


Product Tags:

rcbo circuit breaker

      

earth leakage circuit breaker

      
China NBSM7-45L C16 Residual Current Circuit Device , Residual Current Switch MEM RCBO wholesale

NBSM7-45L C16 Residual Current Circuit Device , Residual Current Switch MEM RCBO Images

Inquiry Cart 0
Send your message to this supplier
 
*From:
*To: Wenzhou New Blue Sky Electrical Co.,Ltd
*Subject:
*Message:
Characters Remaining: (0/3000)